Equipment assembly
Coordinate the switching or protective device with the panel drawing and load schedule.
Four product ranges · Manufacturing and coordinated supply
Series reference image. Appearance, terminals and included accessories vary by configuration. Manufacturer image source ↗
03 / Panel & Distribution Components
DC protective switching for PV, energy-storage and DC distribution panels. This series is selected from the DC system voltage, fault level and protection coordination.
Series selection
| Parameter | Reference data |
|---|---|
| Series | SYM6Z; full frame/trip reference selected for the circuit |
| Rated operating voltage | Up to 1500 V DC |
| Current choices listed | 250 / 320 / 400 / 500 A |
| Pole arrangement | 2-pole DC construction |
| Impulse withstand Uimp | 12 kV |
| Icu at 1500 V DC | 30 kA, time constant τ = 2 ms |
| Ics at 1500 V DC | 25 kA, time constant τ = 2 ms |
| Icu / Ics at 1000 V DC | 50 kA / 50 kA |
The 50 kA figure applies at 1000 V DC, not 1500 V DC. Confirm polarity/terminal wiring, grounding arrangement, time constant, trip settings, isolation duty and accessories with the exact order drawing. A DC rating must not be treated as an AC rating.
Coordinate the switching or protective device with the panel drawing and load schedule.
Use the full nameplate code and installed accessory list to make a precise replacement enquiry.
Use the document for the complete order reference and delivered revision. Manufacturer links open the original source.
A nameplate photograph or equipment list is enough to start. Mingkong provides component sourcing on enquiry; the offered brand, complete code, documentation and delivery terms are confirmed in the quotation.
Use these guides to prepare the information for equipment selection and quotation.