Protection coordination
Review the monitored circuit and trip chain with the equipment protection schedule.
Four product ranges · Manufacturing and coordinated supply
Manufacturer product image. Refer to the order reference for the exact specification. Manufacturer image source ↗
03 / Measurement, Monitoring & Protection
Voltage-sensing monitoring relay for three-phase equipment supplies. Use it in the control circuit to detect incorrect phase sequence or loss of supply phase.
Model specification
| Parameter | Reference data |
|---|---|
| Model | K8AK-PH1 |
| Rated monitored input | 3-phase, 3-wire, 200–480 V AC; 50/60 Hz |
| Internal supply | Taken from the monitored input |
| Output | 1 DPDT relay |
| Resistive contact rating | 5 A at 250 V AC or 30 V DC |
| Input load | Approximately 4.1 VA |
| Reset | Automatic |
| Dimensions (W × H × D) | 22.5 × 90 × 100 mm |
| Mounting | DIN rail |
The relay monitors voltage at its connection point; it does not detect downstream load-side phase loss. The 5 A rating is for a resistive load, not motor switching. Confirm contact duty and the contactor/control circuit. It is not a safety-rated emergency-stop controller.
Review the monitored circuit and trip chain with the equipment protection schedule.
Record the existing settings, wiring and hardware version before selecting a replacement.
Use the document for the complete order reference and delivered revision. Manufacturer links open the original source.
A nameplate photograph or equipment list is enough to start. Mingkong provides component sourcing on enquiry; the offered brand, complete code, documentation and delivery terms are confirmed in the quotation.
Use these guides to prepare the information for equipment selection and quotation.