Building load centres
For commercial centres, hospitals, hotels and high-rise buildings. Selection should consider the electrical load together with the transformer-room footprint, ventilation and required noise limits.
Four product ranges · Manufacturing and coordinated supply

Product illustration. Actual configuration varies by specification.
Open product image ↗Three-dimensional wound-core dry-type transformer for building distribution and infrastructure installations.
Price on enquiry · Configuration, quantity & destination
Supply scope, manufacturer information, applicable documents and warranty arrangements are confirmed in the quotation and order.
The SC(B)12 three-dimensional wound-core transformer combines resin-cast windings with a continuous wound magnetic-core structure. It is intended for building and infrastructure distribution where a dry-type transformer is specified. The wound-core construction is a defining part of the product and should be included in the enquiry and order description.

For commercial centres, hospitals, hotels and high-rise buildings. Selection should consider the electrical load together with the transformer-room footprint, ventilation and required noise limits.

For airports, stations, tunnels and metro-related distribution. Include the available delivery route, cable/busbar interfaces and space for inspection and maintenance.

For coordinated transformer-and-distribution assemblies. Match the transformer envelope and connections with the enclosure and switchgear layout.

The three-dimensional core uses wound silicon-steel material rather than a conventional stacked-core arrangement. Its continuous magnetic path is a central construction feature; the actual no-load loss is identified by the selected rating in the table.
The core construction uses circular cross-sections. The associated winding and support arrangement should be considered as a complete assembly when reviewing dimensions, lifting access and replacement suitability.
Resin is mixed and degassed before casting around the windings. The resulting cast body provides winding insulation, while reinforcing materials within the resin structure contribute to mechanical integrity.
Reinforcing insulation is incorporated around the cast winding structure. Electrical rating, insulation requirements and the specified test programme must be agreed for the delivered configuration.
The table contains 11 ratings from 250 to 2,500 kVA. The 250–500 kVA entries use 4% impedance, while the 630–2,500 kVA entries use 6%. Both the core version and the impedance belong in the technical schedule.

Match the selected transformer to the room layout, terminal arrangement, cooling clearances and approved drawings.
Factory preparation photograph · reference assemblyCompare the capacity and impedance together. You can start an enquiry from a specific row. On a small screen, scroll the table sideways.
| Capacity (kVA) | No-load current (%) | Load loss (W) | No-load loss (W) | Short-circuit impedance (%) | Enquiry |
|---|---|---|---|---|---|
| 250 | 1.10 | 2760 | 575 | 4.0 | Request this rating ↗ |
| 315 | 1.10 | 3470 | 705 | 4.0 | Request this rating ↗ |
| 400 | 1.10 | 3990 | 785 | 4.0 | Request this rating ↗ |
| 500 | 0.85 | 4880 | 930 | 4.0 | Request this rating ↗ |
| 630 | 0.85 | 5960 | 1040 | 6.0 | Request this rating ↗ |
| 800 | 0.85 | 6960 | 1215 | 6.0 | Request this rating ↗ |
| 1000 | 0.85 | 8130 | 1415 | 6.0 | Request this rating ↗ |
| 1250 | 0.85 | 9690 | 1670 | 6.0 | Request this rating ↗ |
| 1600 | 0.85 | 11730 | 1960 | 6.0 | Request this rating ↗ |
| 2000 | 0.70 | 14450 | 2440 | 6.0 | Request this rating ↗ |
| 2500 | 0.70 | 17170 | 2880 | 6.0 | Request this rating ↗ |
Wound-core series table, checked against original PDF page 11. HV: 10 / 6.3 / 6 kV; LV: 0.4 kV; vector groups: Dyn11 / Yyn0; taps: ±5% or ±2 × 2.5%. Use this table only for the wound-core construction.
Send your selected rating and installation requirements to request the matching dimensional drawing, connection details and technical schedule.

Agree the selected specifications, applicable drawings, inspection records and identification requirements in the quotation and order.
Include quantity, destination, packing requirements and preferred trade terms. Confirm transport scope and the requested delivery schedule with the quotation.
For an existing unit, provide its model, nameplate or order reference and a description of the issue. Include relevant photos or records already available. Warranty and service scope follow the agreed order terms.
Contact about this model ↗Choose your enquiry type. Start with the information you have.
Quotations are prepared for the selected configuration, quantity and destination. Currency, validity, delivery terms, freight and any applicable duties or taxes are specified in the quotation.
New installations & project tenders
Discuss a project ↗Send the load schedule, HV/LV voltages, kVA and site conditions. Identify loss limits, vector group and required tests.
Model lists & repeat orders
Discuss supply requirements ↗List preferred kVA and voltage combinations, destination requirements, quantities and spare-parts or documentation needs.
Equipment integration & matching
Discuss an assembly ↗Provide the substation or equipment layout, terminal positions, cooling arrangement and monitoring interfaces.
Identify an existing unit or part
Identify a replacement ↗Send the nameplate, existing dimensions, cable or busbar interfaces and the reason for replacement.
Illustrative enquiry scenarios.
Testing, warranty terms and after-sales scope are to be agreed in the quotation and order documents for the selected configuration.

Construction: Epoxy resin cast
View specifications ↗
Construction: Epoxy resin cast
View specifications ↗
Voltage classes: 10 / 20 / 35 kV
View specifications ↗
Construction: Epoxy resin cast
View specifications ↗Mingkong Transformer Selection Guide · Updated 24 October 2026 · Chinese / English
For a quotation, include your required model, rating, quantity and operating conditions.
Use these guides to prepare the information for equipment selection and quotation.