Medium-voltage Switchgear

KYN28A-12 · Metal-clad withdrawable switchgear

Indoor metal-clad withdrawable switchgear for 12 kV-class distribution.

Voltage designation
3.6 / 7.2 / 12 kV
Selection
Rated current, fault duty and circuit arrangement
Rated current options
630 / 1,250 / 1,600 / 2,000 / 2,500 / 3,150 A
Frequency
50 Hz
Breaking current options
16 / 20 / 25 / 31.5 / 40 / 50 kA
Enquire about KYN28A-12 ↗

Price on enquiry · Configuration, quantity & destination

Supply scope, manufacturer information, applicable documents and warranty arrangements are confirmed in the quotation and order.

APPLICATION & DUTY

Where KYN28A-12 fits

KYN28A-12 is indoor metal-clad withdrawable switchgear for distribution, protection and monitoring. The compartmented design separates busbars, breaker truck, cables and secondary instruments. Main-circuit rating and the actual load-switching duty are selected together.

KYN28A-12 product illustration
Product illustration
APPLICATION / 01

Substation incoming and outgoing circuits

For power receiving and feeder distribution with a defined bus arrangement and protection scheme.

Illustrative industrial infrastructure setting
Application illustration
APPLICATION / 02

Industrial motor and distribution feeders

For plant circuits where the load type and switching frequency form part of the selection, including motor duties requiring a specific review.

PRODUCT ENGINEERING

Construction & operating functions

KYN28A-12 product illustration
KYN28A-12Product illustration · Configuration varies by specification
DETAIL / 01

Four functional compartments

The arrangement separates the busbar, breaker-truck, cable and relay/instrument sections. This organisation helps identify the space and interfaces required for each part of the feeder.

DETAIL / 02

Truck and secondary connection

The breaker truck, shutter and secondary-plug arrangement are part of the withdrawable design. Matching these interfaces is essential for a replacement truck or breaker enquiry.

DETAIL / 03

Earthing and cable equipment

The construction drawing includes the earthing switch, cable terminations, current transformers and surge-protection location. The actual equipment list depends on the selected circuit.

DETAIL / 04

Pressure relief and heating

Pressure-relief and heating provisions are shown in the design. Room layout and auxiliary-supply requirements should accommodate the selected arrangement.

DETAIL / 05

Motor and capacitor duties

Motor and capacitor switching are duty-specific applications. Provide the load characteristics and required operating duty so the appropriate breaker and protective arrangement can be reviewed.

DEFINE THE SELECTED ASSEMBLY

Configuration & installation interfaces

SPECIFICATION & INTEGRATIONReview equipment installation

Match the installation drawing, cable routes, clearances and electrical duty for the selected equipment.

Illustrative working scene
Electrical rating
Select the voltage class, current, short-circuit breaking duty and withstand duty as a matched combination.
Secondary scheme
Provide CT/PT ratios, relay functions, trip/close voltage and remote-control requirements.
Installation
State cable-entry direction, cabinet-lineup and environmental requirements.

Installation & connection checklist

  • Include cable termination sizes and required cable-room space.
  • Provide extension-bus details for additions to an existing lineup.
  • For repairs, send the full breaker reference, truck dimensions and secondary plug photos.
  • Request the selected feeder’s primary and secondary diagrams.
Operating conditions for the listed configuration
  • Indoor installation; altitude up to 1,000 m.
  • Normal ambient range −15 to +40 °C. Special cold-climate configurations require separate agreement.
  • Keep the installation free of significant corrosive or combustible contamination and severe vibration.

State any different ambient temperature, altitude, humidity, dust, salt or corrosive exposure when requesting the installation-specific configuration.

RATING DATA

Technical parameters

9Parameter / configuration entries
Units shownCompare values with their units
Selected variantConfirm the matching configuration

Review the listed configuration and applicable units. On a small screen, scroll the table sideways.

ParameterCatalogue value
Rated voltage options3.6 / 7.2 / 12 kV
Rated frequency50 Hz
Breaker and cabinet current options630 / 1,250 / 1,600 / 2,000 / 2,500 / 3,150 A
Short-circuit breaking current options16 / 20 / 25 / 31.5 / 40 / 50 kA
Short-time withstand (4 s) options16 / 20 / 25 / 31.5 / 40 / 50 kA
Peak withstand/making current options40 / 50 / 63 / 80 / 100 / 125 kA
1 min power-frequency withstand by voltage class24 / 32 / 42 kV
Lightning impulse withstand by voltage class40 / 60 / 75 kV
Enclosure protectionIP4X; IP2X at compartments with the breaker door open

Checked against original distribution catalogue PDF page 15. Insulation values correspond respectively to 3.6, 7.2 and 12 kV classes; select one complete rating combination. Ratings describe catalogue options, not every possible combination; select the complete configuration in the technical schedule.

Drawings & configuration documents

Send your selected rating and installation requirements to request the matching dimensional drawing, connection details and technical schedule.

DOCUMENTS · DELIVERY · SUPPORT

Technical coordination & after-sales enquiries

KYN28A-12 product illustration
KYN28A-12 · Product illustration

Confirm the order documents

Agree the selected specifications, applicable drawings, inspection records and identification requirements in the quotation and order.

Coordinate delivery

Include quantity, destination, packing requirements and preferred trade terms. Confirm transport scope and the requested delivery schedule with the quotation.

Request technical support

For an existing unit, provide its model, nameplate or order reference and a description of the issue. Include relevant photos or records already available. Warranty and service scope follow the agreed order terms.

Contact about this model ↗
START WITH WHAT YOU HAVE

Prepare a quotation for this equipment.

Choose your enquiry type. Start with the information you have.

Price on enquiry

Quotations are prepared for the selected configuration, quantity and destination. Currency, validity, delivery terms, freight and any applicable duties or taxes are specified in the quotation.

Project procurement

New installations & project tenders

Discuss a project ↗
What to prepare

Provide voltage, fault duty, circuit schedule and required protection scheme.

Distributor procurement

Model lists & repeat orders

Discuss supply requirements ↗
What to prepare

List circuit configurations, ratings, preferred components and destination documentation needs.

Panel & equipment builders

Equipment integration & matching

Discuss an assembly ↗
What to prepare

Send the line-up layout, bus interfaces, breaker specification and secondary wiring requirements.

Repair & replacement

Identify an existing unit or part

Identify a replacement ↗
What to prepare

Provide the existing panel and breaker details, dimensions, plug connections and interlocks.

Illustrative enquiry scenarios.

Selection checklist for KYN28A-12
  • System voltage, frequency, rated current and prospective fault level
  • Bus arrangement and incoming/outgoing circuit schedule
  • Breaker or load-switch duty, protection and control supply
  • Cable terminations, room layout, access and expansion requirements
  • Include cable termination sizes and required cable-room space.
  • Provide extension-bus details for additions to an existing lineup.
  • For repairs, send the full breaker reference, truck dimensions and secondary plug photos.
  • Request the selected feeder’s primary and secondary diagrams.

From enquiry to an agreed supply

  1. Share the requirementModel, duty, quantity and destination.
  2. Review the configurationResolve ratings, interfaces and site conditions.
  3. Agree the technical scheduleScope, drawings, tests, price and delivery terms.
  4. Confirm delivery documentsAgree packing, identification and the applicable inspection records.

Testing, warranty terms and after-sales scope are to be agreed in the quotation and order documents for the selected configuration.