KYN28A-24 · Metal-clad withdrawable switchgear

Indoor withdrawable metal-clad switchgear for 24 kV-class applications.

Voltage designation
24 kV
Selection
Rated current, fault duty and circuit arrangement
Rated current options
630 / 1,250 / 1,600 / 2,000 / 2,500 / 3,150 A
Frequency
50 / 60 Hz
Enclosure protection
IP4X
Enquire about KYN28A-24 ↗

Price on enquiry · Configuration, quantity & destination

Supply scope, manufacturer information, applicable documents and warranty arrangements are confirmed in the quotation and order.

APPLICATION & DUTY

Where KYN28A-24 fits

KYN28A-24 is indoor metal-clad withdrawable switchgear for 24 kV three-phase systems. It combines a withdrawable vacuum-breaker arrangement with primary-circuit insulation and secondary protection/control equipment. The configuration is defined by feeder duty, current, fault level and the required control scheme.

KYN28A-24 product illustration
Product illustration
APPLICATION / 01

Power and industrial substations

For receiving and distributing power with switching, protection and monitoring functions.

Illustrative building distribution setting
Application illustration
APPLICATION / 02

Building distribution

For high-rise and large-building installations using a 24 kV distribution arrangement.

PRODUCT ENGINEERING

Construction & operating functions

KYN28A-24 product illustration
KYN28A-24Product illustration · Configuration varies by specification
DETAIL / 01

Withdrawable vacuum breaker

The breaker arrangement is selected together with its truck and cabinet interface. This is especially important when specifying replacements or matching an existing lineup.

DETAIL / 02

Primary-circuit insulation

Bus insulation uses heat-shrink or epoxy-coated arrangements described for the series. The selected insulation and breaker configuration form part of the complete assembly.

DETAIL / 03

Operating interlocks

Interlocking functions address truck movement, earthing and compartment access. The actual combination must match the selected primary and secondary scheme.

DETAIL / 04

Protection and control compartment

Secondary control and protection components are configured around the feeder duty. Supply the required protection functions, CT/PT information and control voltage.

DETAIL / 05

Cabinet-size selection

The table gives two cabinet-width alternatives with corresponding dimensions. Select the physical arrangement together with current rating, cable terminations and installation access.

DEFINE THE SELECTED ASSEMBLY

Configuration & installation interfaces

SPECIFICATION & INTEGRATIONReview equipment installation

Match the installation drawing, cable routes, clearances and electrical duty for the selected equipment.

Illustrative working scene
Rating combination
The table covers 24 kV, 50/60 Hz and several current alternatives. Select the breaking and withstand duties as a consistent combination.
Control supply
DC or AC 110/220 V alternatives are listed; identify the required supply and operating interfaces.
Protection scope
Specify relay functions, metering, communication and interlocking requirements.

Installation & connection checklist

  • Provide room layout, access openings and cable-entry locations.
  • Identify cable sizes and termination arrangements.
  • State bus-extension and cabinet-lineup requirements.
  • For replacement, supply breaker/truck dimensions and the secondary connection diagram.
Operating conditions for the listed configuration
  • Indoor installation; altitude up to 1,000 m.
  • Ambient −15 to +40 °C; 24-hour average up to +35 °C.
  • Daily average relative humidity up to 95%; monthly average up to 90%.

State any different ambient temperature, altitude, humidity, dust, salt or corrosive exposure when requesting the installation-specific configuration.

RATING DATA

Technical parameters

11Parameter / configuration entries
Units shownCompare values with their units
Selected variantConfirm the matching configuration

Review the listed configuration and applicable units. On a small screen, scroll the table sideways.

ParameterCatalogue value
Rated voltage24 kV
Frequency50 / 60 Hz
Rated current options630 / 1,250 / 1,600 / 2,000 / 2,500 / 3,150 A
Short-circuit breaking current options20 / 31.5 kA
Short-time withstand current (4 s)20 / 31.5 kA
Peak withstand current options50 / 80 kA
Auxiliary control voltageDC or AC 110 / 220 V
Auxiliary-circuit power-frequency withstand2,000 V
Enclosure protectionIP4X; IP2X with breaker-compartment door open
Cabinet dimensions (W × D × H)800 × 1,810 × 2,380 or 1,000 × 1,810 × 2,380 mm
Catalogue weight range840–1,440 kg

Checked against original distribution catalogue PDF page 14. 20 kA and 31.5 kA variants correspond to 50 kA and 80 kA peak ratings respectively. Ratings describe catalogue options, not every possible combination; select the complete configuration in the technical schedule.

Drawings & configuration documents

Send your selected rating and installation requirements to request the matching dimensional drawing, connection details and technical schedule.

DOCUMENTS · DELIVERY · SUPPORT

Technical coordination & after-sales enquiries

KYN28A-24 product illustration
KYN28A-24 · Product illustration

Confirm the order documents

Agree the selected specifications, applicable drawings, inspection records and identification requirements in the quotation and order.

Coordinate delivery

Include quantity, destination, packing requirements and preferred trade terms. Confirm transport scope and the requested delivery schedule with the quotation.

Request technical support

For an existing unit, provide its model, nameplate or order reference and a description of the issue. Include relevant photos or records already available. Warranty and service scope follow the agreed order terms.

Contact about this model ↗
START WITH WHAT YOU HAVE

Prepare a quotation for this equipment.

Choose your enquiry type. Start with the information you have.

Price on enquiry

Quotations are prepared for the selected configuration, quantity and destination. Currency, validity, delivery terms, freight and any applicable duties or taxes are specified in the quotation.

Project procurement

New installations & project tenders

Discuss a project ↗
What to prepare

Provide voltage, fault duty, circuit schedule and required protection scheme.

Distributor procurement

Model lists & repeat orders

Discuss supply requirements ↗
What to prepare

List circuit configurations, ratings, preferred components and destination documentation needs.

Panel & equipment builders

Equipment integration & matching

Discuss an assembly ↗
What to prepare

Send the line-up layout, bus interfaces, breaker specification and secondary wiring requirements.

Repair & replacement

Identify an existing unit or part

Identify a replacement ↗
What to prepare

Provide the existing panel and breaker details, dimensions, plug connections and interlocks.

Illustrative enquiry scenarios.

Selection checklist for KYN28A-24
  • System voltage, frequency, rated current and prospective fault level
  • Bus arrangement and incoming/outgoing circuit schedule
  • Breaker or load-switch duty, protection and control supply
  • Cable terminations, room layout, access and expansion requirements
  • Provide room layout, access openings and cable-entry locations.
  • Identify cable sizes and termination arrangements.
  • State bus-extension and cabinet-lineup requirements.
  • For replacement, supply breaker/truck dimensions and the secondary connection diagram.

From enquiry to an agreed supply

  1. Share the requirementModel, duty, quantity and destination.
  2. Review the configurationResolve ratings, interfaces and site conditions.
  3. Agree the technical scheduleScope, drawings, tests, price and delivery terms.
  4. Confirm delivery documentsAgree packing, identification and the applicable inspection records.

Testing, warranty terms and after-sales scope are to be agreed in the quotation and order documents for the selected configuration.