S13-M · Oil-immersed distribution transformer

Sealed oil-immersed distribution transformer with catalogue ratings from 30 to 2,500 kVA and 0.4 kV LV. Review the required primary voltage, winding connection and site conditions before quotation.

Brand
Mingkong
Model
S13-M
Supply
Factory supply
Voltage class
10 kV
Catalogue capacity
30–2,500 kVA
LV rating
0.4 kV
Enquire about S13-M ↗

Price on enquiry · Configuration, quantity & destination

Supply scope, manufacturer information, applicable documents and warranty arrangements are confirmed in the quotation and order.

APPLICATION & DUTY

Where S13-M fits

S13-M is a sealed oil-immersed distribution transformer based on the S13 performance series. The core and winding design is coordinated with capacity-specific loss values. The on-page table provides a practical starting point for comparing the selected capacity, winding connection and impedance.

Illustrative industrial infrastructure setting
Application illustration
APPLICATION / 01

Distribution networks

For urban and rural supply installations requiring a sealed oil-immersed transformer and an agreed electrical schedule.

Illustrative industrial infrastructure setting
Application illustration
APPLICATION / 02

Industrial upgrades

For capacity replacement or new plant distribution. Provide the existing supply details and any changes to connected load or installation layout.

PRODUCT ENGINEERING

Construction & operating functions

S13-M product illustration
S13-MProduct illustration · Configuration varies by specification
DETAIL / 01

Sealed construction

The M suffix identifies a sealed design. The tank outline and accessory arrangement should be reviewed using the drawing for the selected capacity.

DETAIL / 02

Core and winding performance

The S13 series uses its own core/winding performance schedule. No-load loss, load loss and no-load current are separate quantities in the table and should be compared consistently.

DETAIL / 03

Connection-dependent load-loss entries

Up to 500 kVA, the table distinguishes Dyn11 and Yyn0 load losses. Identify the required connection group rather than treating both columns as one interchangeable figure.

DETAIL / 04

Capacity and impedance range

The displayed 30–2,500 kVA entries span 4%, 4.5% and 5% impedance groups. The row-based enquiry retains the capacity and impedance together.

DEFINE THE SELECTED ASSEMBLY

Configuration & installation interfaces

Transformer assembly and cooling equipment during factory preparation
SPECIFICATION & INTEGRATIONReview transformer installation

Match the selected transformer to the room layout, terminal arrangement, cooling clearances and approved drawings.

Factory preparation photograph · reference assembly
Voltage combination
Listed HV alternatives are 6, 6.3, 10, 10.5 and 11 kV; LV is 0.4 kV.
Tap and connection
State the required ±5% or ±2 × 2.5% tapping option, vector group and rated frequency.
Site requirements
Normal conditions include −25 to +40 °C and altitude up to 1,000 m. Describe any different site duty for review.

Installation & connection checklist

  • Provide terminal direction, cable/busbar details and phase arrangement.
  • Include the available footprint and installation-access dimensions.
  • Specify monitoring, protection fittings and required inspection records.
  • For repeat supply, retain the same capacity, impedance, connection group and approved drawing revision.
RATING DATA

Technical parameters

30–2,500 kVACapacity entries in this table
19Listed rating configurations
4.0 / 4.5 / 5.0%Impedance options · see matching row

Compare the capacity and impedance together. You can start an enquiry from a specific row. On a small screen, scroll the table sideways.

Capacity (kVA)No-load current (%)Load loss Dyn11 (W)Load loss Yyn0 (W)No-load loss (W)Short-circuit impedance (%)Enquiry
301.506306001004.0Request this rating ↗
501.309108701304.0Request this rating ↗
631.20109010401504.0Request this rating ↗
801.20131012501804.0Request this rating ↗
1001.10158015002004.0Request this rating ↗
1251.10189018002404.0Request this rating ↗
1601.00231022002804.0Request this rating ↗
2001.00273026003404.0Request this rating ↗
2500.90320030504004.0Request this rating ↗
3150.90383036504804.0Request this rating ↗
4000.80452043005704.0Request this rating ↗
5000.80541051506804.0Request this rating ↗
6300.60620062008104.5Request this rating ↗
8000.60750075009804.5Request this rating ↗
10000.60103001030011504.5Request this rating ↗
12500.50120001200013604.5Request this rating ↗
16000.50145001450016404.5Request this rating ↗
20000.40183001830019405.0Request this rating ↗
25000.40212002120022905.0Request this rating ↗

Checked against the original transformer catalogue, PDF page 24, printed page 38. Through 500 kVA, the source slash-separated loss values correspond to Dyn11 / Yyn0 respectively. Above 500 kVA the source provides one load-loss value, repeated in both columns. HV options: 6 / 6.3 / 10 / 10.5 / 11 kV; taps: ±5% or ±2 × 2.5%; LV: 0.4 kV.

Technical sheets & drawings

Catalogue reference data for the labelled configuration. The agreed technical schedule defines the supplied equipment.

S13-M rating table and vector-group note · original PDF p.24 View referenceS13-M rating table and vector-group note · original PDF p.24
DOCUMENTS · DELIVERY · SUPPORT

Technical coordination & after-sales enquiries

Transformers in the production workshop
Transformer workshop

Confirm the order documents

Agree the selected specifications, applicable drawings, inspection records and identification requirements in the quotation and order.

Coordinate delivery

Include quantity, destination, packing requirements and preferred trade terms. Confirm transport scope and the requested delivery schedule with the quotation.

Request technical support

For an existing unit, provide its model, nameplate or order reference and a description of the issue. Include relevant photos or records already available. Warranty and service scope follow the agreed order terms.

Contact about this model ↗
START WITH WHAT YOU HAVE

Prepare a quotation for this equipment.

Choose your enquiry type. Start with the information you have.

Price on enquiry

Quotations are prepared for the selected configuration, quantity and destination. Currency, validity, delivery terms, freight and any applicable duties or taxes are specified in the quotation.

Project procurement

New installations & project tenders

Discuss a project ↗
What to prepare

Send the load schedule, HV/LV voltages, kVA and site conditions. Identify loss limits, vector group and required tests.

Distributor procurement

Model lists & repeat orders

Discuss supply requirements ↗
What to prepare

List preferred kVA and voltage combinations, destination requirements, quantities and spare-parts or documentation needs.

Panel & equipment builders

Equipment integration & matching

Discuss an assembly ↗
What to prepare

Provide the substation or equipment layout, terminal positions, cooling arrangement and monitoring interfaces.

Repair & replacement

Identify an existing unit or part

Identify a replacement ↗
What to prepare

Send the nameplate, existing dimensions, cable or busbar interfaces and the reason for replacement.

Illustrative enquiry scenarios.

Selection checklist for S13-M
  • Required kVA, HV/LV voltages, frequency and vector group
  • Tapping arrangement, impedance and required loss limits
  • Indoor/outdoor site, ambient temperature, altitude and ventilation
  • Cable or busbar connections, installation dimensions, monitoring and test documents
  • Provide terminal direction, cable/busbar details and phase arrangement.
  • Include the available footprint and installation-access dimensions.
  • Specify monitoring, protection fittings and required inspection records.
  • For repeat supply, retain the same capacity, impedance, connection group and approved drawing revision.

From enquiry to an agreed supply

  1. Share the requirementModel, duty, quantity and destination.
  2. Review the configurationResolve ratings, interfaces and site conditions.
  3. Agree the technical scheduleScope, drawings, tests, price and delivery terms.
  4. Confirm delivery documentsAgree packing, identification and the applicable inspection records.

Testing, warranty terms and after-sales scope are to be agreed in the quotation and order documents for the selected configuration.