Distribution networks
For urban and rural supply installations requiring a sealed oil-immersed transformer and an agreed electrical schedule.
Four product ranges · Manufacturing and coordinated supply

Product illustration. Actual configuration varies by specification.
Open product image ↗Sealed oil-immersed distribution transformer with catalogue ratings from 30 to 2,500 kVA and 0.4 kV LV. Review the required primary voltage, winding connection and site conditions before quotation.
Price on enquiry · Configuration, quantity & destination
Supply scope, manufacturer information, applicable documents and warranty arrangements are confirmed in the quotation and order.
S13-M is a sealed oil-immersed distribution transformer based on the S13 performance series. The core and winding design is coordinated with capacity-specific loss values. The on-page table provides a practical starting point for comparing the selected capacity, winding connection and impedance.

For urban and rural supply installations requiring a sealed oil-immersed transformer and an agreed electrical schedule.

For capacity replacement or new plant distribution. Provide the existing supply details and any changes to connected load or installation layout.

The M suffix identifies a sealed design. The tank outline and accessory arrangement should be reviewed using the drawing for the selected capacity.
The S13 series uses its own core/winding performance schedule. No-load loss, load loss and no-load current are separate quantities in the table and should be compared consistently.
Up to 500 kVA, the table distinguishes Dyn11 and Yyn0 load losses. Identify the required connection group rather than treating both columns as one interchangeable figure.
The displayed 30–2,500 kVA entries span 4%, 4.5% and 5% impedance groups. The row-based enquiry retains the capacity and impedance together.

Match the selected transformer to the room layout, terminal arrangement, cooling clearances and approved drawings.
Factory preparation photograph · reference assemblyCompare the capacity and impedance together. You can start an enquiry from a specific row. On a small screen, scroll the table sideways.
| Capacity (kVA) | No-load current (%) | Load loss Dyn11 (W) | Load loss Yyn0 (W) | No-load loss (W) | Short-circuit impedance (%) | Enquiry |
|---|---|---|---|---|---|---|
| 30 | 1.50 | 630 | 600 | 100 | 4.0 | Request this rating ↗ |
| 50 | 1.30 | 910 | 870 | 130 | 4.0 | Request this rating ↗ |
| 63 | 1.20 | 1090 | 1040 | 150 | 4.0 | Request this rating ↗ |
| 80 | 1.20 | 1310 | 1250 | 180 | 4.0 | Request this rating ↗ |
| 100 | 1.10 | 1580 | 1500 | 200 | 4.0 | Request this rating ↗ |
| 125 | 1.10 | 1890 | 1800 | 240 | 4.0 | Request this rating ↗ |
| 160 | 1.00 | 2310 | 2200 | 280 | 4.0 | Request this rating ↗ |
| 200 | 1.00 | 2730 | 2600 | 340 | 4.0 | Request this rating ↗ |
| 250 | 0.90 | 3200 | 3050 | 400 | 4.0 | Request this rating ↗ |
| 315 | 0.90 | 3830 | 3650 | 480 | 4.0 | Request this rating ↗ |
| 400 | 0.80 | 4520 | 4300 | 570 | 4.0 | Request this rating ↗ |
| 500 | 0.80 | 5410 | 5150 | 680 | 4.0 | Request this rating ↗ |
| 630 | 0.60 | 6200 | 6200 | 810 | 4.5 | Request this rating ↗ |
| 800 | 0.60 | 7500 | 7500 | 980 | 4.5 | Request this rating ↗ |
| 1000 | 0.60 | 10300 | 10300 | 1150 | 4.5 | Request this rating ↗ |
| 1250 | 0.50 | 12000 | 12000 | 1360 | 4.5 | Request this rating ↗ |
| 1600 | 0.50 | 14500 | 14500 | 1640 | 4.5 | Request this rating ↗ |
| 2000 | 0.40 | 18300 | 18300 | 1940 | 5.0 | Request this rating ↗ |
| 2500 | 0.40 | 21200 | 21200 | 2290 | 5.0 | Request this rating ↗ |
Checked against the original transformer catalogue, PDF page 24, printed page 38. Through 500 kVA, the source slash-separated loss values correspond to Dyn11 / Yyn0 respectively. Above 500 kVA the source provides one load-loss value, repeated in both columns. HV options: 6 / 6.3 / 10 / 10.5 / 11 kV; taps: ±5% or ±2 × 2.5%; LV: 0.4 kV.
Explore transformer manufacturing ↗ · View equipment & application references ↗

Agree the selected specifications, applicable drawings, inspection records and identification requirements in the quotation and order.
Include quantity, destination, packing requirements and preferred trade terms. Confirm transport scope and the requested delivery schedule with the quotation.
For an existing unit, provide its model, nameplate or order reference and a description of the issue. Include relevant photos or records already available. Warranty and service scope follow the agreed order terms.
Contact about this model ↗Choose your enquiry type. Start with the information you have.
Quotations are prepared for the selected configuration, quantity and destination. Currency, validity, delivery terms, freight and any applicable duties or taxes are specified in the quotation.
New installations & project tenders
Discuss a project ↗Send the load schedule, HV/LV voltages, kVA and site conditions. Identify loss limits, vector group and required tests.
Model lists & repeat orders
Discuss supply requirements ↗List preferred kVA and voltage combinations, destination requirements, quantities and spare-parts or documentation needs.
Equipment integration & matching
Discuss an assembly ↗Provide the substation or equipment layout, terminal positions, cooling arrangement and monitoring interfaces.
Identify an existing unit or part
Identify a replacement ↗Send the nameplate, existing dimensions, cable or busbar interfaces and the reason for replacement.
Illustrative enquiry scenarios.
Testing, warranty terms and after-sales scope are to be agreed in the quotation and order documents for the selected configuration.

Catalogue capacity: 30–1,600 kVA
View specifications ↗
Catalogue capacity: 30–1,600 kVA
View specifications ↗
S13 table HV options: 20 / 22 / 24 kV
View specifications ↗
Voltage class: 35 kV
View specifications ↗Mingkong Transformer Selection Guide · Updated 24 October 2026 · Chinese / English
For a quotation, include your required model, rating, quantity and operating conditions.
Use these guides to prepare the information for equipment selection and quotation.