SC(B)13 · Cast-resin dry-type transformer

Cast-resin dry-type transformer for building load centres and infrastructure distribution.

Brand
Mingkong
Model
SC(B)13
Supply
Factory supply
Construction
Epoxy resin cast
LV rating
0.4 kV
Vector groups
Dyn11 / Yyn0
Enquire about SC(B)13 ↗

Price on enquiry · Configuration, quantity & destination

Supply scope, manufacturer information, applicable documents and warranty arrangements are confirmed in the quotation and order.

APPLICATION & DUTY

Where SC(B)13 fits

SC(B)13 is a resin-cast dry-type transformer series for building load centres and infrastructure distribution. Its capacity-specific loss schedule allows procurement teams to compare electrical performance at the chosen rating. The final selection also includes the voltage combination, vector group, impedance, connection arrangement and installation environment.

Illustrative building distribution setting
Application illustration
APPLICATION / 01

Commercial and public facilities

For hospitals, hotels, theatres and commercial centres. Provide the required transformer-room arrangement and any building-specific monitoring or acoustic requirements.

Illustrative industrial infrastructure setting
Application illustration
APPLICATION / 02

Urban infrastructure

For stations, airports, tunnels and combined substations. Review electrical rating, installation envelope and connection access together.

PRODUCT ENGINEERING

Construction & operating functions

SC(B)13 product illustration
SC(B)13Product illustration · Configuration varies by specification
DETAIL / 01

Cast-resin winding insulation

The winding insulation uses an epoxy-resin casting process. Resin mixing and vacuum degassing prepare the mixture before casting, helping the insulation surround the winding and fill the spaces within the assembly.

DETAIL / 02

Reinforced winding construction

Reinforcing insulation materials are incorporated within the cast winding structure. The filled resin and reinforcement form a coordinated mechanical assembly around the winding; required short-circuit and insulation test documents should be specified for the selected design.

DETAIL / 03

Low-voltage winding selection

A foil-type low-voltage winding is an option identified in the series designation. Confirm the actual winding construction with the selected capacity, voltage combination and technical schedule.

DETAIL / 04

Series-specific loss schedule

No-load loss and load loss are shown separately from no-load current. Use the SC(B)13 data for the required rating when comparing offers and specify the reference temperature in the technical schedule.

DETAIL / 05

Impedance options at the same capacity

The two 630 kVA rows represent different impedance configurations. Capacity alone therefore does not define an identical unit; the row-based enquiry retains both capacity and impedance.

DETAIL / 06

Configuration continuity for repeat supply

Keep the voltage combination, vector group, impedance and auxiliary requirements with the approved drawing. This makes a repeated order more precise than ordering by SC(B)13 and kVA alone.

DEFINE THE SELECTED ASSEMBLY

Configuration & installation interfaces

Transformer assembly and cooling equipment during factory preparation
SPECIFICATION & INTEGRATIONReview transformer installation

Match the selected transformer to the room layout, terminal arrangement, cooling clearances and approved drawings.

Factory preparation photograph · reference assembly
Voltage and vector group
HV options shown are 10, 6.3 and 6 kV; LV is 0.4 kV. Select Dyn11 or Yyn0 as required by the system.
Tapping and thermal duty
Specify tapping range, frequency, cooling duty and any enclosure-related installation constraints.
Acceptance schedule
Identify required loss limits, inspection records and project-specific test documentation before the order is agreed.

Installation & connection checklist

  • Provide cable or busbar termination details and connection direction.
  • Include access, ventilation and maintenance space in the room layout.
  • Specify temperature indication and external alarm/trip contacts where required.
  • Send the existing nameplate and dimensions for replacement enquiries.
RATING DATA

Technical parameters

30–2,500 kVACapacity entries in this table
19Listed rating configurations
4.0 / 6.0%Impedance options · see matching row

Compare the capacity and impedance together. You can start an enquiry from a specific row. On a small screen, scroll the table sideways.

Capacity (kVA)No-load current (%)Load loss (W)No-load loss (W)Short-circuit impedance (%)Enquiry
302.006401354.0Request this rating ↗
502.009001954.0Request this rating ↗
801.5012402654.0Request this rating ↗
1001.5014102904.0Request this rating ↗
1251.3016603404.0Request this rating ↗
1601.3019103854.0Request this rating ↗
2001.1022704454.0Request this rating ↗
2501.1024805154.0Request this rating ↗
3151.0031206354.0Request this rating ↗
4001.0035907054.0Request this rating ↗
5001.0043908354.0Request this rating ↗
6300.8552909654.0Request this rating ↗
6300.8553609356.0Request this rating ↗
8000.85626010906.0Request this rating ↗
10000.85731012706.0Request this rating ↗
12500.85872015006.0Request this rating ↗
16000.851050017606.0Request this rating ↗
20000.701300021906.0Request this rating ↗
25000.701540025906.0Request this rating ↗

10 kV-class catalogue table, checked against original PDF page 12. HV options: 10 / 6.3 / 6 kV; LV: 0.4 kV; vector groups: Dyn11 / Yyn0. Select the impedance and tapping arrangement together with the capacity. Loss-reference temperature and the final technical schedule are to be agreed.

Drawings & configuration documents

Send your selected rating and installation requirements to request the matching dimensional drawing, connection details and technical schedule.

DOCUMENTS · DELIVERY · SUPPORT

Technical coordination & after-sales enquiries

Transformers in the production workshop
Transformer workshop

Confirm the order documents

Agree the selected specifications, applicable drawings, inspection records and identification requirements in the quotation and order.

Coordinate delivery

Include quantity, destination, packing requirements and preferred trade terms. Confirm transport scope and the requested delivery schedule with the quotation.

Request technical support

For an existing unit, provide its model, nameplate or order reference and a description of the issue. Include relevant photos or records already available. Warranty and service scope follow the agreed order terms.

Contact about this model ↗
START WITH WHAT YOU HAVE

Prepare a quotation for this equipment.

Choose your enquiry type. Start with the information you have.

Price on enquiry

Quotations are prepared for the selected configuration, quantity and destination. Currency, validity, delivery terms, freight and any applicable duties or taxes are specified in the quotation.

Project procurement

New installations & project tenders

Discuss a project ↗
What to prepare

Send the load schedule, HV/LV voltages, kVA and site conditions. Identify loss limits, vector group and required tests.

Distributor procurement

Model lists & repeat orders

Discuss supply requirements ↗
What to prepare

List preferred kVA and voltage combinations, destination requirements, quantities and spare-parts or documentation needs.

Panel & equipment builders

Equipment integration & matching

Discuss an assembly ↗
What to prepare

Provide the substation or equipment layout, terminal positions, cooling arrangement and monitoring interfaces.

Repair & replacement

Identify an existing unit or part

Identify a replacement ↗
What to prepare

Send the nameplate, existing dimensions, cable or busbar interfaces and the reason for replacement.

Illustrative enquiry scenarios.

Selection checklist for SC(B)13
  • Required kVA, HV/LV voltages, frequency and vector group
  • Tapping arrangement, impedance and required loss limits
  • Indoor/outdoor site, ambient temperature, altitude and ventilation
  • Cable or busbar connections, installation dimensions, monitoring and test documents
  • Provide cable or busbar termination details and connection direction.
  • Include access, ventilation and maintenance space in the room layout.
  • Specify temperature indication and external alarm/trip contacts where required.
  • Send the existing nameplate and dimensions for replacement enquiries.

From enquiry to an agreed supply

  1. Share the requirementModel, duty, quantity and destination.
  2. Review the configurationResolve ratings, interfaces and site conditions.
  3. Agree the technical scheduleScope, drawings, tests, price and delivery terms.
  4. Confirm delivery documentsAgree packing, identification and the applicable inspection records.

Testing, warranty terms and after-sales scope are to be agreed in the quotation and order documents for the selected configuration.