Buildings and transport facilities
For transformer installations serving hospitals, commercial centres, stations, airports and similar electrical loads.
Four product ranges · Manufacturing and coordinated supply

Product illustration. Actual configuration varies by specification.
Open product image ↗Non-encapsulated dry-type transformer with an impregnated insulation system for building and industrial installations.
Price on enquiry · Configuration, quantity & destination
Supply scope, manufacturer information, applicable documents and warranty arrangements are confirmed in the quotation and order.
SG(B)10 is a non-encapsulated dry-type transformer with an impregnated winding insulation system. It is used for building and industrial power distribution where winding construction, thermal class and installation conditions need to be specified together. The performance table distinguishes the loss reference temperatures for the listed insulation classes.

For transformer installations serving hospitals, commercial centres, stations, airports and similar electrical loads.

For plants where the insulation system, load duty and site environment are defined in the project specification.

The high-voltage winding uses a continuous construction. Winding geometry and insulation treatment form part of the transformer’s electrical and thermal design.
The low-voltage winding is foil wound, with ceramic supports used in the winding assembly. Terminal details and mounting arrangements should be reviewed on the selected unit’s drawing.
The winding system is treated by vacuum impregnation and curing. NOMEX insulation is identified for the construction; specify the intended insulation system and thermal class in the order schedule.
The table lists B/100 °C, F/120 °C and H/145 °C load-loss columns. These reference temperatures are distinct from the insulation class designation and must accompany comparisons.

Match the selected transformer to the room layout, terminal arrangement, cooling clearances and approved drawings.
Factory preparation photograph · reference assemblyCompare the capacity and impedance together. You can start an enquiry from a specific row. On a small screen, scroll the table sideways.
| Capacity (kVA) | No-load loss (W) | Load loss B / 100°C (W) | Load loss F / 120°C (W) | Load loss H / 145°C (W) | Short-circuit impedance (%) | Enquiry |
|---|---|---|---|---|---|---|
| 250 | 720 | 2590 | 2760 | 2960 | 4.0 | Request this rating ↗ |
| 315 | 880 | 3270 | 3470 | 3730 | 4.0 | Request this rating ↗ |
| 400 | 980 | 3750 | 3990 | 4280 | 4.0 | Request this rating ↗ |
| 500 | 1160 | 4590 | 4880 | 5230 | 4.0 | Request this rating ↗ |
| 630 | 1340 | 5530 | 5880 | 6290 | 4.0 | Request this rating ↗ |
| 630 | 1300 | 5610 | 5960 | 6400 | 6.0 | Request this rating ↗ |
| 800 | 1520 | 6550 | 6960 | 7460 | 6.0 | Request this rating ↗ |
| 1000 | 1770 | 7650 | 8130 | 8760 | 6.0 | Request this rating ↗ |
| 1250 | 2090 | 9100 | 9690 | 10370 | 6.0 | Request this rating ↗ |
| 1600 | 2450 | 11000 | 11700 | 12500 | 6.0 | Request this rating ↗ |
| 2000 | 3050 | 13600 | 14400 | 15500 | 6.0 | Request this rating ↗ |
| 2500 | 3600 | 16100 | 17100 | 18400 | 6.0 | Request this rating ↗ |
| 2000 | 3050 | 15000 | 15900 | 17100 | 8.0 | Request this rating ↗ |
| 2500 | 3600 | 17700 | 18800 | 20200 | 8.0 | Request this rating ↗ |
Checked against original PDF page 15. B, F and H loss columns use reference temperatures of 100, 120 and 145 °C respectively. Only the listed capacity/impedance combinations are shown; request a technical schedule for other configurations.
Send your selected rating and installation requirements to request the matching dimensional drawing, connection details and technical schedule.

Agree the selected specifications, applicable drawings, inspection records and identification requirements in the quotation and order.
Include quantity, destination, packing requirements and preferred trade terms. Confirm transport scope and the requested delivery schedule with the quotation.
For an existing unit, provide its model, nameplate or order reference and a description of the issue. Include relevant photos or records already available. Warranty and service scope follow the agreed order terms.
Contact about this model ↗Choose your enquiry type. Start with the information you have.
Quotations are prepared for the selected configuration, quantity and destination. Currency, validity, delivery terms, freight and any applicable duties or taxes are specified in the quotation.
New installations & project tenders
Discuss a project ↗Send the load schedule, HV/LV voltages, kVA and site conditions. Identify loss limits, vector group and required tests.
Model lists & repeat orders
Discuss supply requirements ↗List preferred kVA and voltage combinations, destination requirements, quantities and spare-parts or documentation needs.
Equipment integration & matching
Discuss an assembly ↗Provide the substation or equipment layout, terminal positions, cooling arrangement and monitoring interfaces.
Identify an existing unit or part
Identify a replacement ↗Send the nameplate, existing dimensions, cable or busbar interfaces and the reason for replacement.
Illustrative enquiry scenarios.
Testing, warranty terms and after-sales scope are to be agreed in the quotation and order documents for the selected configuration.

Construction: Epoxy resin cast
View specifications ↗
Construction: Epoxy resin cast
View specifications ↗
Voltage classes: 10 / 20 / 35 kV
View specifications ↗
Construction: Epoxy resin cast
View specifications ↗Mingkong Transformer Selection Guide · Updated 24 October 2026 · Chinese / English
For a quotation, include your required model, rating, quantity and operating conditions.
Use these guides to prepare the information for equipment selection and quotation.