Buildings with varying loads
For commercial buildings, hospitals and transport facilities. Include the expected load profile, ventilation arrangement and installation environment.
Four product ranges · Manufacturing and coordinated supply

Product illustration. Actual configuration varies by specification.
Open product image ↗H-class non-encapsulated dry-type transformer for building and industrial distribution.
Price on enquiry · Configuration, quantity & destination
Supply scope, manufacturer information, applicable documents and warranty arrangements are confirmed in the quotation and order.
SG(Z)(B)11 is a non-encapsulated H-class dry-type transformer family using an impregnated insulation system. It is intended for building and industrial distribution. The full model configuration should identify whether on-load regulation is required, as well as the winding connection, voltage combination and thermal duty.

For commercial buildings, hospitals and transport facilities. Include the expected load profile, ventilation arrangement and installation environment.

For plant transformer installations where insulation construction, load duty and voltage regulation need to be coordinated.

The windings use a NOMEX-based insulation system. The selected construction combines the insulation materials with impregnation and curing to form the winding assembly.
Repeated impregnation and heat curing are described for the winding system. This differs from a fully resin-encapsulated winding and is an important construction detail for specification.
The high-voltage winding uses a continuous structure with heat-dissipation considerations. Cooling, enclosure and the actual site temperature should be reviewed together.
The model description includes Z for on-load voltage regulation. Specify whether this function is required and include the tap range and control requirements in the enquiry.

Match the selected transformer to the room layout, terminal arrangement, cooling clearances and approved drawings.
Factory preparation photograph · reference assemblyCompare the capacity and impedance together. You can start an enquiry from a specific row. On a small screen, scroll the table sideways.
| Capacity (kVA) | No-load current (%) | Load loss (W) | No-load loss (W) | Short-circuit impedance (%) | Enquiry |
|---|---|---|---|---|---|
| 30 | 2.4 | 760 | 170 | 4.0 | Request this rating ↗ |
| 50 | 2.4 | 1070 | 240 | 4.0 | Request this rating ↗ |
| 80 | 1.8 | 1480 | 330 | 4.0 | Request this rating ↗ |
| 100 | 1.8 | 1690 | 360 | 4.0 | Request this rating ↗ |
| 125 | 1.6 | 1980 | 420 | 4.0 | Request this rating ↗ |
| 160 | 1.6 | 2280 | 480 | 4.0 | Request this rating ↗ |
| 200 | 1.4 | 2710 | 550 | 4.0 | Request this rating ↗ |
| 250 | 1.4 | 2960 | 640 | 4.0 | Request this rating ↗ |
| 315 | 1.2 | 3730 | 790 | 4.0 | Request this rating ↗ |
| 400 | 1.2 | 4280 | 880 | 4.0 | Request this rating ↗ |
| 500 | 1.2 | 5230 | 1040 | 4.0 | Request this rating ↗ |
| 630 | 1.0 | 6290 | 1200 | 4.0 | Request this rating ↗ |
| 630 | 1.0 | 6400 | 1170 | 6.0 | Request this rating ↗ |
| 800 | 1.0 | 7460 | 1360 | 6.0 | Request this rating ↗ |
| 1000 | 1.0 | 8760 | 1590 | 6.0 | Request this rating ↗ |
| 1250 | 1.0 | 10370 | 1880 | 6.0 | Request this rating ↗ |
| 1600 | 1.0 | 12580 | 2200 | 6.0 | Request this rating ↗ |
| 2000 | 0.8 | 15560 | 2740 | 6.0 | Request this rating ↗ |
| 2500 | 0.8 | 18450 | 3240 | 6.0 | Request this rating ↗ |
| 2000 | 0.8 | 17110 | 2740 | 8.0 | Request this rating ↗ |
| 2500 | 0.8 | 20290 | 3240 | 8.0 | Request this rating ↗ |
Checked against original PDF page 16. HV: 6–10 kV; taps: ±2 × 2.5%; LV: 0.4 kV; vector groups: Yyn0 / Dyn11. Only the listed capacity/impedance combinations are shown.
Send your selected rating and installation requirements to request the matching dimensional drawing, connection details and technical schedule.

Agree the selected specifications, applicable drawings, inspection records and identification requirements in the quotation and order.
Include quantity, destination, packing requirements and preferred trade terms. Confirm transport scope and the requested delivery schedule with the quotation.
For an existing unit, provide its model, nameplate or order reference and a description of the issue. Include relevant photos or records already available. Warranty and service scope follow the agreed order terms.
Contact about this model ↗Choose your enquiry type. Start with the information you have.
Quotations are prepared for the selected configuration, quantity and destination. Currency, validity, delivery terms, freight and any applicable duties or taxes are specified in the quotation.
New installations & project tenders
Discuss a project ↗Send the load schedule, HV/LV voltages, kVA and site conditions. Identify loss limits, vector group and required tests.
Model lists & repeat orders
Discuss supply requirements ↗List preferred kVA and voltage combinations, destination requirements, quantities and spare-parts or documentation needs.
Equipment integration & matching
Discuss an assembly ↗Provide the substation or equipment layout, terminal positions, cooling arrangement and monitoring interfaces.
Identify an existing unit or part
Identify a replacement ↗Send the nameplate, existing dimensions, cable or busbar interfaces and the reason for replacement.
Illustrative enquiry scenarios.
Testing, warranty terms and after-sales scope are to be agreed in the quotation and order documents for the selected configuration.

Construction: Epoxy resin cast
View specifications ↗
Construction: Epoxy resin cast
View specifications ↗
Voltage classes: 10 / 20 / 35 kV
View specifications ↗
Construction: Epoxy resin cast
View specifications ↗Mingkong Transformer Selection Guide · Updated 24 October 2026 · Chinese / English
For a quotation, include your required model, rating, quantity and operating conditions.
Use these guides to prepare the information for equipment selection and quotation.